1. What I will do in case of Ingition failure? 2. What I will do if Blower Fan running failure occurs? 3. What I will do if Fuel Oil Pump delivery failure occurs? 4. What I will do in case of unsteady flame? 5. What I will do if there is no response to flame by automatic furnace controller with flame sensor? 6. What I will do if Defuser Assembly / Burner Head give poor combustion data due to heavy inside accumulation of oil or coke (oil operation)? 7. What I will do if Solenoid Valve fails to open? 8. Give me cleaning and lubricating instructions
Ans 6. What I will do if Defuser Assembly / Burner Head give poor combustion data due to heavy inside accumulation of oil or coke (oil operation)?
Cause
Remedy
Incorrect settings
Correct settings
Incorrect mixture ignition unit
Replace unit
Nozzle too large or too small
Replace nozzle
Incorrect angle or spray
High or low combustion air flow rate
Readjust burner
Furnace chamber not sufficiently ventilated
Furnace chamber to be ventilated through a non-closed opening with a cross section of minimum 50 % of all chimney cross sections of the furnace system. Take care to observe the application regulations
Defective coil
Replace coil
Defective automatic furnace controller
Replace automatic furnace controller
Valve does not close tightly; dirt accumulated on sealing surfaces
Open valve; remove foreign matter; replace valve if required